Make your own free website on Tripod.com


 

           Һչ (¢ͧŴ)
  1.Input Circuit
    LOD 01
OUT 200
END
     
  2.AND Circuit 1
    LOD N 01
AND 02
OUT 200
END
     
  3.AND Circuit 2 (Series Circuit)
    LOD 01
AND 02
AND N 03
OUT 200
END
     
  4.OR Circuit 1 (Parallel Circuit)
    LOD 01
OR 02
OUT 200
END
     
  5.OR Circuit 2 (Parallel Circuit)
    LOD 01
OR 02
OR N 03
OR 04
OUT 200
END
     
  6.Self Holding Circuit 1(With Priority to RESET)
    LOD 01
OR 200
AND N 02
OUT 200
END
     
  7.Self Holding Circuit 2 (Whit Priority to SET)
    LOD 01
LOD 200
AND N 02
OR LOD
OUT 200
END
     
  8.Priority Circuit 1 (Continuous Input Signal)
    LOD 01
AND N 201
OUT 200
LOD 02
AND N 200
OUT 201
END
     
  9.Priority Circuit 2 (Pulse Input Signal)
    LOD 01
OR 200
AND N 201
AND N 03
OUT 200
LOD 02
OR 201
AND N 200
AND N 03
OUT 201
END
     
  10.Series Paraleel Circuit 1
    LOD 01
AND N 02
OR 03
OUT 200
END
     
  11.Series Parallel Circuit 2
    LOD 01
AND N 02
OR 03
AND N 04
AND 05
OUT 200
END
     
  12.Series Parallel Circuit (OR LOD) 3
    LOD 01
LOD 02
AND 03
OR LOD
AND 04
OUT 200
END
     
  13.Series Parallel Circuit (OR LOD) 4
    LOD 01
LOD 02
AND N 03
OR 04
OR LOD
AND 05
OUT 200
END
     
  14.Series Parallel Circuit (OR LOD) 5
    LOD 01
AND 02
LOD 03
AND N 04
OR LOD
AND 05
OUT 200
END
     
  15.Series Parallel Circuit (OR LOD) 6
    LOD 01
AND 02
LOD N 03
AND 04
OR LOD
LOD 05
AND 06
OR LOD
AND 07
AND N 10
OUT 200
END
     
  16.Series Parallel Circuit (AND LOD) 1
    LOD 01
AND N 02
LOD 03
OR 04
AND LOD
OUT 200
END
     
  17.Series Parallel Circuit (AND LOD) 2
    LOD 01
AND 02
LOD N 03
AND 04
OR 05
AND LOD
OUT 200
END
     
  18.Series Parallel Circuit (AND LOD) 3
    LOD 01
OR 02
LOD 03
OR 04
AND LOD
OUT 200
END
     
  19.Series Parallel Circuit (AND LOD & OR LOD) 4
    LOD 01
OR 02
LOD 03
AND 04
LOD N 05
AND 06
OR LOD
AND LOD
OUT 200
END
     
  20.Series Parallel Circuit (AND LOD & OR LOD) 5
    LOD 01
AND 02
LOD 03
AND 04
OR LOD
LOD 05
AND 06
LOD 07
AND N 10
OR LOD
AND LOD
OUT 200
END
     
  21.Multiple Output Circuit 1
    LOD 01
OUT 200
AND N 02
OUT 201
AND 03
OUT 202
END
     
  22.Multiple Output Circuit
    LOD 01
OR 02
OR 03
OR 04
AND 05
OUT 200
AND 02
OUT 201
LOD 200
AND 03
OUT 202
END
     
  23.()Complex Circuit 1
    LOD 01
LOD 02
AND 03
LOD 04
LOD 05
OR 06
AND LOD
OR LOD
AND LOD
AND N 07
OUT 200
END
     
  23.()
    LOD 02
AND 03
LOD 05
OR 06
AND 04
OR LOD
AND 01
AND N 07
OUT 200
END
     
  24.Complex Circuit 2
    LOD 01
LOD 02
OR 03
AND LOD
AND 04
LOD 05
AND N 06
OR LOD
OR 07
AND N 10
OUT 200
END
     
  25.()ON Delay Timer
    LOD 01
TIM 1
100
LOD T 1
OUT 200
END
     
  25.()
    LOD 01
TIM 0
100
OUT 200
END
     
  26.OFF Delay Timer
()Flicker Circuit
    LOD N T 3
TIM 3
10
END
     
  ()Constant Frequency Pulse Generating Circuit
    LOD 01
AND N T 4
TIM 4
100
LOD N T 4
AND 200
LOD T 4
AND N 200
OR LOD
AND 01
OUT 200
END
     
  ()Adjustable Duty Ratio Pulse Generating Circuit
    LOD 01
AND N T 6
TIM 5
50
OUT 200
TIM 6
100
END
     
  28.Long Delay Timer 1 (Timer + Timer)
    LOD 01
TIM 7
9000
TIM 8
3000
OUT 200
END
     
  29.Long Delay Timer 2 (Timer + Counter)
    LOD 01
AND N T 9
TIM 9
60
LOD N 01
LOD T 9
CNT 0
OUT 200
END
     
  30.Circuit to Turn Output Off Temporarily after Timer up
    LOD 01
TIM 10
100
AND N 02
OUT 200
END
     
  31.Timer Using Special Internal Relay IR 714 (1 sec clock)
    LOD N 01
LOD 01
AND 714
CNT 1
600
OUT 200
END
     
  32.ON/OFF Delay Circuit
    LOD 01
TIM 11
100
LOD 200
AND N 01
TIM 12
50
LOD T 11
OR 200
AND N T 12
OUT 200
END
     
  33.Adding Counter 1
    LOD 01
LOD 02
CNT 2
9
OUT 200
END
     
  34.Adding Counter 2 (Multi Stage Setting One Shot Output Circuit)
    LOD 01
LOD 02
CNT 3
10
OUT 200
FUN 103
2
OUT 201
FUN 103
5
OUT 202
FUN 103
7
OUT 203
END
     
  35.Adding Counter 3 (Multi Stage Setting Seft Holding Output Circuit)
    LOD 01
LOD 02
CNT 4
10
OUT 200
FUN 204
3
OUT 201
FUN 204
5
OUT 202
FUN 204
8
OUT 203
END
     
  36.Adding Counter 4 (Larger/Smallet Comparison Circuit
    LOD 01
AND N 03
AND N 04
AND N 05
AND N 06
LOD 02
CNT 5
500
FUN 205
5
OUT 400
FUN 205
15
AND N 400
OUT 200
END
     
  37.Multi Digit Counter 1
    LOD 01
LOD 02
CNT 6
9999
LOD 01
LOD 02
AND C 6
CNT 7
1002
OUT 200
END
     
  38.Multi Digit Counter 2 (7 digit setting)
    LOD 01
OR C 8]
LOD 02
CNT 8
1000
LOD 01
LOD C 8
CNT 9
9999
END
     
  39.Dual Input Reversible Counter Circuit (CNT45)
    LOD 01
LOD 02
LOD 03
CNT 45
1000
OUT 200
FUN 245
1012
OUT 201
END
     
  40.Gate Controlled Reversible Counter Circuit (CNT46)
    LOD 01
LOD 02
LOD 03
CNT 46
20
OUT 200
FUN 146
10
OUT 201
FUN 246
15
OUT 202
END
     
  41.Forward Shift Register Circuit
    LOD 01
LOD 02
LOD 03
SFR 0
8
OUT 200
LOD R 0
OUT 201
LOD R 2
OUT 202
LOD R 5
OUT 203
END